4-64
09-Communication Parameters
09-00
Assigned Communication Station Number
Range
1 ~ 32
09-00 sets the communication station number when more than one unit on the communication network. Up
to 32 inverters can be controlled from one master controller such as a PLC.
09-01
RTU code /ASCII code Selection
Range
0:RTU
1:ASCII
2:BACnet
09-02
Baud Rate Setting (bps)
Range
0: 4800
1: 9600
2: 19200
3: 38400
09-03
Stop Bit Selection
Range
0: 1 stop bit
1: 2 stop bit
09-04
Parity Selection
Range
0: No parity
1: Even parity
2: Odd parity
09-05
Data Format Selection
Range
0: 8 bit data
1: 7 bit data
Set 09-01~09-05 to configure communication format before communicating the inverter.
09-06
Communication time-out detection time
Range
0.0~25.5Sec
09-07
Communication time-out operation selection
Range
0: Stop in deceleration time 1 and show COT after communication timeout
1: Stop in free run mode and show COT after communication timeout
2: Stop in deceleration time 2 and show COT after communication timeout
3: Keep running and show COT after Communication timeout
Time-out detection time: 00.0~25.5 seconds; setting 0.0 seconds disables time-out function.
09-08
Err6 fault tolerance times
Range
1~20
When communication error time ≥ 09-08 setting the keypad display shows ERR6.