4-61
Example 4&5 .
Auto Run Mode 06-00=1~3. After a restart continues to run from the unfinished step.
Auto Run Mode 06-00=4~6. After a restart, it will begin a new cycle.
06- 00
1~3 4~6
Output Frequency
ACC/DEC time in Auto run mode will be according to the setting of 00-14/00-15 or 00-16/00-17.
For Auto sequence 0.The run frequency will be according to keypad frequency set by parameter
05-01.Parameters 06-16 and 06-32 are used to set the sequence Run time and Run direction.
time
Output
Frequency
Run
Command
Continue running from
unfinished step
stop runrun
time
Output
Frequency
Run
Command
begin a new cycle
stop runrun