App 3-7
(Note) Err6 error: Inverter gets communication error with external devices.
When inverter gets communication error:
If the controller writes “1” to “2501H bit 2”, inverter appears “EFO” on display.
If the controller does not write “1” to “2501H bit 2”, inverter appears “Err6” on display
Register No.
Content
2523H Frequency command(100/1Hz)
2524H Output frequency (100/1Hz)
2525H Output voltage command (10/1V)
2526H DC voltage command (1/1V)
2527H
Output current (10/1A)
2528H
Reserved
2529H
Output power (10/1 kW)
252AH
PID feedback (100% / fmax , 10/1% )
252BH
PID input (100% / fmax, 10/1%)
252CH
TM2 AVI input value (1000 / 10V) *1
252DH
TM2 ACI input value (1000 / 10V) *1
252EH
Reserved
252FH
A510s / L510s / E510s identification
L510s standard type: 0x0110
L510s PUMP function built-in: 0x0111
2530H
Reserved
2531H
Inverter temperature(10/°C)(temperature of heat sink or IGBT)
2532H
The ratio of inverter and motor rated current (%)
2522H
Sequence input status
0 Terminal S1 1 :“ON” 0:“OFF”
1 Terminal S2 1 :“ON” 0:“OFF”
2 Terminal S3 1 :“ON” 0:“OFF”
3 Terminal S4 1 :“ON” 0:“OFF”
4 Terminal S5 1 :“ON” 0:“OFF”
5 Terminal S6 1 :“ON” 0:“OFF”
Contact output
6 Relay R1 1 :“ON” 0:“OFF”
7 Relay R2 1 :“ON” 0:“OFF”
9~F Reserved