App 3-20
3. BACnet Specifications
Inverter L510s model is built-in standard BACnet MS/TP communication protocol structure to
meet the demand of automatic communication equipment. Control or monitor L510s via
BACnet to be allowable to read and modify specific parameter. L510s includes the
following supports of standard objects:
■ Inverter Objects
■ Analog Input ■ Analog Output ■ Analog Value
■ Digital Input ■ Digital Output ■ Digital Value
Refer to Table 3.1 for L510s supporting the property information of object classification. User
can collect related properties of objects required via the dedicated communication software of
BACnet to give control or monitor command for each object.
Table 3.1 Object and property supporting list
Proerty
Inverter
(DEV)
Analog
Input
(AI)
Analog
Output
(AO)
Analog
Value
(AV)
Digital
Input
(BI)
Digital
Output
(BO)
Digital
Value
(BV)
Object_Identifier V V V V V V V
Object_Name V V V V V V V
Object_Type V V V V V V V
System_Status V
Vendor_Name V
Vendor_ Identifier V
Model_Name V
Firmware_Revision V
Applocation_Software_Supported V
Protocol_Version V
Protocol_Revision V
Protocol_Services_Supported V
Protocol_Object_Type_Supported V
Object_List V
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Max_Masters V
Max_Info_Frames V
Device_Address_Binding
Location V
Presnent_Value V V V V V V
Status_Flags
Event_State
Relibility
Out_Of_Service
Units V V V
Priority_Array
Relinquish_Default
Polarity
Inactive_Text
Active_Text