App 3-23
No. Object Name Description Unit
Classifica
tion
Range
AO13 FreqCommand7
Speed frequency
setting-stage 6
HZ R/W 0 - 599
AO14 FreqCommand8
Speed frequency
setting-stage 7
HZ R/W 0 - 599
AO23 RunMode
Main run command
source selection
No Units R/W 0 - 2
AO24 ReverseOper
Direction locked
command
No Units R/W 0 - 1
AO25 StoppingSel Stop modes selection No Units R/W 0 - 1
AO26 FrequenceComm
Main frequency
command source
selection
No Units R/W 0 - 6
AO27 FreqUpperLim Upper limit frequency HZ R/W 0.01 - 599
AO28 FreqLowerLim Lower limit frequency HZ R/W 0 – 598.99
AO29 Acc Time1 Acceleration time 1 seconds R/W 0.1 - 3600
AO30 Dec Time1 Deceleration time 1 seconds R/W 0.1 - 3600
Table 4.4 Analog value property list (READ/ WRITE)
No. Object Name Description Unit
Classifica
tion
Range
AV0 PID – P Gain Proportional gain (P) No Units R/W 0 - 10
AV1 PID – I Time Integral time (I) No Units R/W 0 - 100
AV2 PID – D Time Differential time (D) No Units R/W 0 – 10
Table 4.5 Digital input property list (READ)
No. Object Name Description Unit
Classifi
cation
Range
BI0 Run/Stop Operation status Stop / Run R 0 - 1
BI1 Direction Operation direction FWD/REV R 0 - 1
BI2 ststus Inverter status OK/Fault R 0 - 1
BI3 Abnormal Error occurs Close/Open R 0 - 1
BI4 DI_1 status S1 status Close/Open R 0 - 1
BI5 DI_2 status S2 status Close/Open R 0 - 1
BI6 DI_3 status S3 status Close/Open R 0 - 1
BI7 DI_4 status S4 status Close/Open R 0 - 1
BI8 DI_5 status S5 status Close/Open R 0 - 1
Table 4.6 Digital output property list (READ/ WRITE)
No. Object Name Description Unit Classification Range
BO0 RY1 status
Relay output 1
status
Close/Open R 0 - 1
Table 4.7 Digital value property list (READ/ WRITE)
No. Object Name Description Unit Classification Range
BV0 RUN/STOP RUN/STOP Stop / Run R/W 0 - 1
BV1 FWD/REV FWD/REV FWD/REV R/W 0 - 1