App 3-22
Table 4.2 Analog input property list (READ)
No.
Object
Name
Description Unit Classification Range
AI0 TM2 AVI AVI input Percent R 0 - 100
AI1 TM2 ACI ACI input Percent R 0 - 100
AI2 Error code Recent fault message No Units R 0 –43
AI3 Freq cmd Frequency command HZ R 0 - 599
AI4 Frequency Output frequency HZ R 0 -599
AI5 Current Output current Amps R
AI6
Control
Mode
Control mode No Units R 0 - 1
AI7 Motor R-Volt Motor rated voltage Volt R
AI8 Motor R-HP Motor rated power horsepower R
AI9
Motor R-
RPM
Motor rated rotation
speed
rpm R
AI10 Motor R-Hz Motor rated frequency HZ R
AI11 CarrierFreq Carrier frequency KiloHertz R 1 - 16
AI12
Comm
Station
INV communication
station
No Units R 1 – 32
AI13 BaudRate Baudrate setting No Units R 0 – 3
AI14 BacnetSel
Communication mode
selection
No Units R 0 – 2
AI15 DevInstance Inverter number No Units R 1 - 254
Table 4.3 – Analog output property list (READ/ WRITE)
No. Object Name Description Unit
Classifica
tion
Range
AO0 Set Frequency Frequency command HZ R/W 0 - 599
AO1 AO Output voltage Volt R 0 - 10
AO3 Motor R-Amp Motor rated current Amps R/W 0-65535
AO4 PwrL Sel
Momentary stop and
restart selection
No Units R 0 - 1
AO5 RestartSel
Number of Fault Auto-
Restart Attempts
No Units R 0 – 10
AO6 RestartDelay
Fault Auto-Restart
Time
seconds R 0 - 800
AO7 FreqCommand1
Speed frequency
setting-stage 0
HZ R/W 0 - 599
AO8 FreqCommand2
Speed frequency
setting-stage 1
HZ R/W 0 - 599
AO9 FreqCommand3
Speed frequency
setting-stage 2
HZ R/W 0 - 599
AO10 FreqCommand4
Speed frequency
setting-stage 3
HZ R/W 0 - 599
AO11 FreqCommand5
Speed frequency
setting-stage 4
HZ R/W 0 - 599
AO12 FreqCommand6
Speed frequency
setting-stage 5
HZ R/W 0 - 599