4-13 
Group 03-    Multi function Di
ital Inputs/Outputs 
No. Description  Range 
Factory 
Setting 
Unit Note
03-00 
Multifunction Input Term. S1  0: Forward/Stop Command 
1: Reverse/Stop Command 
2: Preset Speed 1 (5-02) 
3: Preset Speed 2 (5-03) 
4: Preset Speed 4 (5-05) 
6: Jog Forward Command 
7: Jog Reverse Command 
8: Up Command 
9: Down Command 
10: Acc/Dec 2 
11: Acc/Dec Disabled 
12: Main/Alternative Run Command select 
13: Main/Alternative Frequency Command 
select 
14: Rapid Stop ( Decel to stop) 
15: Base Block 
16: Disable PID Function   
17: Reset 
18: Auto Run Mode enable   
19: Forced Frequency Run(pump model only) 
20: Switch to Constant Pressure 2(pump   
model only) 
0 
-   
03-01 
Multifunction Input Term. S2 
1 
-   
03-02 
Multifunction Input Term. S3 
2 -  
03-03 
Multifunction Input Term. S4 
3 -  
03-04 
Multifunction Input Term. S5 
17 - Note1
03-05 
Reserved 
03-06 
Up/Down frequency band  0.00~5.00 0.00 Hz  
03-07 
Up/Down Frequency modes 
0: Preset frequency is held as the inverter   
stops, and UP/Down function is disabled. 
1: Preset frequency is reset to 0 Hz as the 
inverter stops. 
2: Preset frequency is held as the inverter 
stops, and the UP/Down is available.     
0 - 
 
03-08 
S1~S5 scan confirmation    1~200.    Number of Scan cycles  10  2ms  
03-09 
S1~ S5 switch type select 
xxxx0:S1 NO     xxxx1:S1 NC 
xxx0x:S2 NO    xxx1x:S2 NC 
xx0xx:S3 NO     xx1xx:S3 NC 
x0xxx:S4 NO    x1xxx:S4 NC 
0xxxx:S5 NO    1xxxx:S5 NC 
00000 - 
 
03-10 
Reserved 
03-11 
Output Relay(RY1) 
0: Run 
1: Fault 
2: Setting Frequency Reached 
3: Frequency Reached (3-13±3-14) 
4: Output Frequency Detection1(> 3-13) 
5: Output Frequency Detection2(< 3-13) 
6: Auto-Restart 
7: Momentary AC Power Loss 
8: Rapid Stop 
9: Base Block 
10: Motor Overload Protection(OL1) 
11: Drive Overload Protection(OL2) 
12: Reserved 
13: Output Current Reached 
14: Brake Control 
15: PID feedback disconnection detection 
16: High Pressure Detection 
17: Low Pressure Detection 
18: Pressure Loss Detection 
1 - 
Note1
03-12 
Reserved 
03-13 
Output frequency detection 
0.00~599.00 0.00 Hz *1