4-13
Group 03- Multi function Di
g
ital Inputs/Outputs
No. Description Range
Factory
Setting
Unit Note
03-00
Multifunction Input Term. S1 0: Forward/Stop Command
1: Reverse/Stop Command
2: Preset Speed 1 (5-02)
3: Preset Speed 2 (5-03)
4: Preset Speed 4 (5-05)
6: Jog Forward Command
7: Jog Reverse Command
8: Up Command
9: Down Command
10: Acc/Dec 2
11: Acc/Dec Disabled
12: Main/Alternative Run Command select
13: Main/Alternative Frequency Command
select
14: Rapid Stop ( Decel to stop)
15: Base Block
16: Disable PID Function
17: Reset
18: Auto Run Mode enable
19: Forced Frequency Run(pump model only)
20: Switch to Constant Pressure 2(pump
model only)
0
-
03-01
Multifunction Input Term. S2
1
-
03-02
Multifunction Input Term. S3
2 -
03-03
Multifunction Input Term. S4
3 -
03-04
Multifunction Input Term. S5
17 - Note1
03-05
Reserved
03-06
Up/Down frequency band 0.00~5.00 0.00 Hz
03-07
Up/Down Frequency modes
0: Preset frequency is held as the inverter
stops, and UP/Down function is disabled.
1: Preset frequency is reset to 0 Hz as the
inverter stops.
2: Preset frequency is held as the inverter
stops, and the UP/Down is available.
0 -
03-08
S1~S5 scan confirmation 1~200. Number of Scan cycles 10 2ms
03-09
S1~ S5 switch type select
xxxx0:S1 NO xxxx1:S1 NC
xxx0x:S2 NO xxx1x:S2 NC
xx0xx:S3 NO xx1xx:S3 NC
x0xxx:S4 NO x1xxx:S4 NC
0xxxx:S5 NO 1xxxx:S5 NC
00000 -
03-10
Reserved
03-11
Output Relay(RY1)
0: Run
1: Fault
2: Setting Frequency Reached
3: Frequency Reached (3-13±3-14)
4: Output Frequency Detection1(> 3-13)
5: Output Frequency Detection2(< 3-13)
6: Auto-Restart
7: Momentary AC Power Loss
8: Rapid Stop
9: Base Block
10: Motor Overload Protection(OL1)
11: Drive Overload Protection(OL2)
12: Reserved
13: Output Current Reached
14: Brake Control
15: PID feedback disconnection detection
16: High Pressure Detection
17: Low Pressure Detection
18: Pressure Loss Detection
1 -
Note1
03-12
Reserved
03-13
Output frequency detection
0.00~599.00 0.00 Hz *1