4-22
Group 09- Communication function setup
No. Description Range
Factory
Setting
Unit Note
09-00
Assigned Communication
Station Number
1 ~ 32 1 - *2*3
09-01
Communication Mode Select
0: Modbus RTU code
1: Modbus ASCII code
2: BACnet (Pump application built-in
without this function)
0 -
*2*3
Note1
09-02
Baud Rate Setting (bps)
0: 4800
1: 9600
2: 19200
3: 38400
2 bps *2*3
09-03
Stop Bit Selection
0: 1 Stop Bit
1: 2 Stop Bits
0 - *2*3
09-04
Parity Selection
0: Without Parity
1: With Even Parity
2: With Odd Parity
0 - *2*3
09-05
Data Format Selection
0: 8-Bits Data
1: 7-Bits Data
0 - *2*3
09-06
Communication time-out
detection time
0.0 ~ 25.5
0.0 s
09-07
Communication time-out
operation selection
0: Deceleration to stop (set by 00-15)
1: Coast to stop
2: Deceleration to stop (set by 00-17)
3: continue operating
0 -
09-08
Error 6 verification time. 0 ~ 20
3
09-09
Drive Transmit delay Time(ms) 5 ~ 65
5 2ms
09-10
BACnet stations
1~254(Pump application built-in
without this function)
1
*2*3
Note1