4-45
03- 06 Up/Down frequency step
Range
0.00~5.00Hz
Example: S1: 03- 00=8Up frequency command, S203- 01=9Down frequency command,
03- 06=Hz
Mode1: If UP or DOWN input terminals are turned on for less than 2 seconds, for every On operation
frequency changes by Hz.
S1
S2
ON ON ON
Hz
T
Hz
Actual output
frequency
ON ON ON
Hz
Mode 2: If UP or DOWN input terminals are turned on for more than 2Seconds, the original
UP/DOWN mode is restored Output frequency Ramps up or down as long as the input is
kept ON.
As shown in the diagram below.
S1
S2
ON ON
ON
>2Sec
OFF
OFF
>2Sec
T
Hz
ON
03- 07 Up/Down keep Frequency status after a stop command
Range
0: After a stop command in Up/Down mode, the preset frequency is held
as the inverter stops, and the UP/Down function is disabled.
1: After a stop command in Up/Down mode, the preset frequency is reset
to 0 Hz as the inverter stops.
2: After a stop command in Up/Down mode, the preset frequency is held
as the inverter stops, and the UP/Down function remains enabled.
03 - 07=0, 2 when run signal is removed (Stop Command), the output frequency is stored in
parameter 05-01( Key pad Frequency).
03 - 07=0, in stop mode since frequency can not be increased or decreased from Up/Down
terminals then keypad can be used to change the frequency by modifying parameter 05-01.
03 - 07=1, In Up/down frequency mode inverter will ramp up from 0Hz on Run command
and Ramp down to 0 Hz on stop command.