4-46
03- 08 Multifunction terminals S1~S5 scan time
Range
【1~200】 2ms
Multifunction input terminal On/Off periods will be scanned for the number of cycles according
to the set value in parameter 03-08. If the signal status for On or off period is less than the set
period it will be treated as noise.
Scan period unit is 1ms.
Use this parameter if unstable input signal is expected, however setting long scan time periods
results in slower response times.
03- 09 s1~s5 Input type selection NO & NC
Range
【xxxx0】:S1 NO 【xxxx1】:S1 NC
【xxx0x】:S2 NO 【xxx1x】:S2 NC
【xx0xx】:S3 NO 【xx1xx】:S3 NC
【x0xxx】:S4 NO 【x1xxx】:S4 NC
【0xxxx】:S5 NO 【1xxxx】:S5 NC
(NO) Normally open, (NC) Normally closed. Select as required.
For selecting Normally Open (NO) or Normally Closed(NC) set the relevant digit in
parameter 03-09 to 0 or 1 as required.
Set Parameter 03-09 first before you use the Parameters 00-02/00-03=1 to set the
inverter run mode to External multifunction inputs.
03-11 Multifunction Output Relay RY1 functions. ( Terminals RB, RA )
Range
【0】:Run
【1】:Fault
【2】:Setting Frequency Reached ---------------------------( refer to 03-14)
【3】:Frequency Reached (3-13±3-14) ---------------------( refer to 03-13/03-14)
【4】:Output Frequency Detection 1 (> 03-13) ----------( refer to 03-13)
【5】:Output Frequency Detection 2 (< 03-13) ----------( refer to 03-13)
【6】:Auto-Restart
【7】:Momentary AC Power Loss----------------------------( refer to 07-00)
【8】:Rapid Stop (Decelerate to Stop)
【9】:Base Block
【10】:Motor Overload Protection (OL1)
【11】:Drive Overload Protection (OL2)
【12】:Reserved
【13】:Output Current Reached ----------------------------(refer to 03-15/03-16)
【14】:Brake Control--------------------------------------------(refer to 03-17/03-18)
【15】:PID Feedback Disconnection Detection --------(refer to 10-11/10-13)
【16】:High Pressure Detection
【17】:Low Pressure Detection
【18】:Pressure Loss Detection
03-13 Frequency Detection Level
Range
【0.00~599.00】 Hz
03-14 Frequency Detection Width
Range
【0.00~30.00】 Hz