4-47
Output relay RY1. function descriptions:
1) 03-11 =0. RY1 will be ON with Run signal.
2) 03-11 =1. RY1 will be ON with inverter Faults.
3) 03-11 =2. RY1 will be ON when Output Frequency reached Setting Frequency.
ExampleSetting Freq. =30, and Frequency Detection Width (03-14) =5,
Relay will be ON when output frequency reached 25Hz to 30Hz and Run Command
is on (Allowable tolerance ±0.01).
4) 03-11=3RY1 will be ON when Setting Freq. and Output Frequency reached (03-13 +/- 03-
14).
Example:
Frequency Detection Level (03-13) =30, and Frequency Detection Width (03-14) =5 cause
Frequency Detection Range upper limit = 35, and Frequency Detection Range lower limit
= 25. So RY1 will be on when Setting Freq. and Output Freq. are both under these limits;
on the other hand, RY1 will be off when Setting Freq. and Output Freq. are not under
these limits either.