4-48
5) 03-11=【4】. RY1 will be on while Output Freq. > Frequency Detection Level (03-13).
6) 03-11=【5】. RY1 will be on while Output Freq. < Frequency Detection Level (03-13).
7) 03-11=【16】, High Pressure Detection, please refer parameter setting of 14-12~14-14
8) 03-11=【17】, Low Pressure Detection, please refer parameter setting of 14-15~14-17
9) 03-11=【18】,
Pressure Loss Detection, please refer parameter setting of 14-18~14-19
03-15
Output Current Detection Level
Range
【0.1~999.9】 A
03-16
Output Current Detection Period
Range
【0.1~10.0】Sec
03-11=【13】.RY1 will be on as soon as the output current value > Output current
detection level (03-15).
03-15: Setting range (0.1~15.0 Amps) as required according to the rated motor current.
03-16: Setting range (0.1~10.0) unit: seconds.