4-50
03-18
03-17
RUN command
03-11=14
Hz
T
ON
OFF
RUN STOP
03- 19 Relay Output Status type
Range
【0】:A (Normally open)
【1】:B (Normally close)
03- 20 Brake Transistor ON Level
Range
100V/200V:【240.0~400.0】VDC
400V:【500.0~800.0】VDC
03- 21 Brake Transistor OFF Level
Range
100V/200V:【240.0~400.0】VDC
400V:【500.0~800.0】VDC
When DC bus voltage >03-20, Excess voltage will be applied to the external brake resistor.
When DC bus voltage <= 03-21, Braking transistor will be switched off.
Do not set 03-21 > 03-20, or display will show Err2, which means parameter setting error.