4-12
Group 03- Multi-Speed Parameters
Code
Parameter Name Setting Range Default
Unit Attribute
03-31
Acceleration Time Setting of
Multi Speed 7
0.1 ~ 3600.0 10.0 Sec
*1
03-32
Deceleration Time Setting of
Multi Speed 7
0.1 ~ 3600.0 10.0 Sec
*1
03-33~03-48 Reserved
Group
Start/stop command group
Code Parameter Name Setting Range Default Unit Attribute
04-01
Stopping Method
Selection
0: Enhanced braking capacity
0 -
1: Coast to stop
04-02 Reserved
04-03
Momentary Power Loss
and Restart
0: Momentary Power Loss and Restart disable
0 -
1: Momentary power loss and restart enable
04-04~04-07 Reserved
04-08
Reset Mode Setting
0: Enable Reset Only when Run Command is Off
0 -
1: Enable Reset when Run Command is On or
Off
04-09
Direct Running After
Power Up
0: Enable Direct running after power up
1 -
1:
Disable Direct running after power up
04-10~04-14 Reserved
04-15
DC Injection Brake Start
Frequency @stopped
0.10 ~ 10.00 1.5 Hz
04-16
DC Injection Brake
Level @stopped
0 ~ 20 5 %
04-17
DC Injection Brake
Time@stopped
0.0 ~ 25.5 0.5 Sec
04-18
DC Injection
Brake@running
0:DC Injection Brake @running enable
0 -
1:DC Injection Brake @ running disable
04-19
Brake chopper enable
alignment
400V:550.0~800.0
690
V
04-20
STP2 enable
0:enable 1:disable 1
Group
V/F command group
Code Parameter Name Setting Range Default Unit Attribute
05-00 Reserved
05-01
No-load Current of Motor -----
Amps
*5
05-02
Motor rated Slip Compensation
0.0 ~100.0 0.0
% *5
05-03
V/f max voltage
400.0V:323.0~528.0
380.0 Vac
05-04
Maximum Frequency
0.20 ~ 400.00
50.00/60
.00
Hz *5
05-05
Maximum Frequency Voltage
400V:0.0 ~ 528.0 380.0
Vac *5
05-06
Medium Frequency2
0.10 ~ 400.00
2.50/3.0
0
Hz *5
05-07
Medium Frequency Voltage 2
400V:0.0 ~ 528.0 30.4
Vac
*5
05-08
Medium Frequency1
0.10 ~ 400.00
2.50/3.0
0
Hz *5
05-09
Medium Frequency Voltage 1
400V:0.0 ~ 528.0 30.4
Vac *5