4-13
Group 05- V/F command group
Code Parameter Name Setting Range Default Unit Attribute
05-10
Minimum Frequency
0.10 ~400.00 1.50 Hz *5
05-11
Minimum Frequency Voltage
400V:0.0 ~ 528.0 22.8
Vac
*5
05-12 Reserved
05-13
Slip compensation Low-pass
Filter time
0.05 ~10.00 0.10
mS *5
05-14 Reserved
05-15
Auto-Torque compensation
Filter time coefficient
0.1~1000.0 0.1
- *1*5
05-16
Auto-Torque compensation
gain
0~200 35
% *1*5
05-17
Auto-Torque compensation
frequency
1.00~5.00 1.00
Hz *1
Group 06- Motor Parameters
Code
Parameter Name Setting Range Default Unit Attribute
06-00
Motor rated voltage
-----
Vac *4
06-01
Motor rated current -----
A *4
06-02
Motor rated power -----
kW *4
06-03
Motor rated Speed -----
RPM
*4
06-04
Motor rated Frequency -----
Hz *4
06-05
Motor parameters automatic
tuning
0: Disable
0
1: Perform static self-learning of motor
parameters
06-06
Stator resistance gain -----
Rs *4
06-07
Rotor resistance gain
-----
Rr *4
06-08
Equivalent inductance gain -----
1kg *4
06-09
Magnetizing current gain -----
imag
*4
06-10
Iron loss conductance gain
-----
gm *4
06-11
Deadtime gain
0~100 100
*4
Group 07- Protection Parameters
Code
Parameter Name Setting Range Default Unit Attribute
07-00
Stall Prevention Function
xxxx0: Stall prevention is enabled in
acceleration
00000 - *1
xxxx1: Stall prevention is disabled in
acceleration.
xxx0x: Stall prevention is enabled in
deceleration.
xxx1x: Stall prevention is enabled in
deceleration.
xx0xx: Stall prevention is enabled in
operation
xx1xx: Stall prevention is disabled in
operation
x0xxx: Enable over voltage Prevention
in deceleration
x1xxx: Disable over voltage Prevention
in deceleration
07-01
Stall Prevention Level During
Acceleration (%)
50 ~ 200 160 %
07-02
Stall Prevention Level During
deceleration (%)
50 ~ 200 160 %