4-47
13-00 = 3(or 6)
Panel Frequency (3-01)=15 Hz 13-01=30Hz 13-02=50Hz 13-15=20Hz
13-16=20s 13-17=25s 13-18=30s 13-23=40s
13-32=1 13-33=1 13-34 = 1 13-39=1(FWD)
13-03~13-06=0Hz ,13-19~13-22=0s ,13-35~13-39 = 0
Note:13-00 = 1~3 : If the inverter stops and re-starts, it will continue running from the unfinished step,
according to the setting of 13-00.
= 4~6: If the inverter stops and re-starts, it will begin a new cycle and continue running
according to the setting of 13-00
1~3 4~6
Output Frequency
time
Output
Frequency
Run
Command
Continue running from
unfinished step
stop runrun
time
Output
Frequency
Run
Command
begin a new cycle
stop runrun
●ACC/DEC time follow the setting of 00-09/00-10 or 10-05/10-06 in Auto Run Mode.
Note: 13-16, and 13-32, need to cooperate with panel frequency (3-01) as the 0th speed of
automatic program operation.