1.4.3 Fuse types 
Drive input fuses are provided to disconnect the drive from power in the event that a component fails in the 
drive’s power circuitry. The drive’s electronic protection circuitry is designed to clear drive output short circuits 
and ground faults without blowing the drive input fuses. Below table shows the 7200GS/GS510 input fuse 
ratings. 
To protect the inverter most effectively, use fuses with current-limit function.
 
 
220V class 
MODEL 
HP  KVA 
AMPS 
Rated Input AMPS  FUSE Rating 
JNTEBG□□7R50JK 
7.5  10.3  24 
29  50 
JNTEBG□□0010JK 
10  13.7  32 
38  60 
JNTEBG□□0015JK 
15  20.6  48 
58  100 
JNTEBG□□0020JK 
20  27.4  64 
77  125 
JNTEBG□□0025JK 
25  34  80 
88  125 
JNTEBG□□0030JK 
30  41  96 
106  150 
JNTEBG□□0040JK 
40  54  130 
143  200 
JNTEBG□□0050JK 
50  57  160 
176  250 
JNTEBG□□0060JK 
60  67  183 
201  300 
JNTEBG□□0075JK 
75  85  224 
246  350 
JNTEBG□□0100JK 
100  128  300 
330  450 
 
440V class 
MODEL 
HP  KVA 
AMPS 
Rated Input AMPS  FUSE Rating 
JNTEBG□□7R50AZ 
7.5  10.3  12 
14  25 
JNTEBG□□0010AZ 
10  13.7  16 
19  30 
JNTEBG□□0015AZ 
15  20.6  24 
29  50 
JNTEBG□□0020AZ 
20  27.4  32 
38  60 
JNTEBG□□0025AZ 
25  34  40 
48  70 
JNTEBG□□0030AZ 
30  41  48 
53  80 
JNTEBG□□0040AZ 
40  54  64 
70  100 
JNTEBG□□0050AZ 
50  68  80 
88  125 
JNTEBG□□0060AZ 
60  82  96 
106  150 
JNTEBG□□0075AZ 
75  110  128 
141  200 
JNTEBG□□0100AZ 
100  138  165 
182  250 
JNTEBG□□0125AZ 
125  180  192 
211  300 
JNTEBG□□0150AZ 
150  195  224 
246  350 
JNTEBG□□0175AZ 
175  230  270 
297  400 
JNTEBG□□0215AZ 
215  260  300 
330  450 
JNTEBG□□0250AZ 
250  290  340 
374  500 
JNTEBG□□0300AZ 
300  385  450 
540  700 
JNTEBG□□0400AZ 
400  513  600 
720  900 
JNTEBG□□0500AZ 
500  561  660 
805  1000 
Fuse Type        UL designated SEMICONDUCTOR PROTECTION FUSES 
   Class   CC, J, T, RK1 or RK5 
   Voltage Range:  300V for drives with 220V class VFD 
       600V for drives with 440V class VFD