44 
 
4. FAULT DISPLAY AND TROUBLESHOOTING 
The 7200GS/GS510 has protection function and warning self-diagnosis function. If a fault a occurs, the 
protection functions operate to shut off the inverter output and the motor coasts to a stop, at the same time, the 
fault contact signal (terminal R3A-R3C, R3B-R3C) is output. 
A). PROTECTION FUNCTION AND TROUBLESHOOTING 
Protection function  Explanation  LCD display (English)
Low 
voltage 
protection
Main circuit 
low voltage 
When the inverter power voltage drops, torque becomes insufficient and motor is 
overheated. 
Inverter output is stopped when the main circuit DC voltage becomes lower than 
the low voltage detection level for 15 ms or longer. or about 2 seconds or longer if 
the momentary power loss redo-thru function is used. 
Detection level: Approximately 210V or less for 200V class 
and 420V or less for 400V class 
Fault (UV1)*
1
 
DC Volt. Low 
 
Momentary 
power loss 
protection 
Control circuit 
low voltage 
The inverter output is shut-off when he control circuit voltage drops below the low 
voltage level. 
Fault (UV2)*
 
Cont. Ckt Low Volt.
Man circuit 
soft charge 
contactor 
The inverter output is shut-off when no answer back is received from the main 
circuit soft-start contactor. 
Fault (UV3)*
1
 
MC Ans. Fault 
Overcurrent protection 
The inverter output is shut-off when the inverter output current becomes approx. 
200% and above of inverter rated current. 
Fault (OC)*
1
 
Over Current 
 
Ground-fault protection 
The inverter output is shut-off when a ground-fault occurs at the inverter output 
side and the ground-fault current exceeds approximately 50% of the inverter rated 
current. 
Fault (GF)*
1
 
Ground Short 
 
Overvoltage protection 
The inverter output is shut-off when the main circuit DC voltage becomes 
excessive because or regeneration energy caused by motor deceleration and 
negative load. 
Detection. Approx. 800V for input voltage set 400V and above 
Level    : Approx. 700V for input voltage set 400V or less and approx. 400V for 
200V class 
Fault (OV)*
1
 
Over Voltage 
 
Cooling fin overheat 
The inverter output is shut-off when the ambient temperature rises and the heat 
sink fin reaches 105℃. Please check for a detective cooling fan or clogged filter. 
Fault (OH)*
1
 
Over Heat 
 
Overload 
protection
Motor 
Inverter output is stopped when motor overload is detected by the electronic 
thermal overload in the inverter. Either a inverter duty constant-torque specialized 
motor or general-purpose motor can 9 selected. If more than one motor is driven. 
overload protection should be disabled. Use a thermal relay or thermal protector for 
each motor. 
Fault (OL1)*
1
 
Motor Over Load 
 
Inverter 
The inverter output is shut-off when the electronic thermal overload reaches or 
exceeds the inverse time limit of 103% of the inverter's rated current occurs. 
Maximum rated overload: 110%. 1 min. 
Fault (OL2)*
1
 
Inverter Over Load 
Over torque 
detection 
The motor operates according to a preset mode when the inverter output current 
execeeds the overtorque detection level. This function is used to protect the 
machine or to monitor the output torque. 
Fault (OL3)*
1
 
Over Torque 
External 
fault signal 
input 
Terminal ○
3
 
When an external alarm signal is input. the inverter operates according to a preset 
stop method (coasting to a stop, continuous operation. or ramp to stop) 
Fault (EF3)*
 
 
Terminal ○
5
 
Fault (EF5)*
 
Terminal ○
6
 
Fault (EF6)*
 
Terminal ○
7
 
Fault (EF7)*
 
Terminal ○
8
 
Fault (EF8)*
 
Control 
Circuit 
Fault 
Control Circuit 
The inverter output is shut-off when a transmission error occurs in the control 
circuit or a component fails. The inverter output is also shut-off when a specialized 
option such as the digital operator is not properly connected. 
Fault (CPF02)*
 
 
EEPROM fault
Fault (CPF03)*
 
EEPROM 
BCC CODE 
Fault (CPF04)*
1
 
EEPROM CODE Err.
CPU ADC 
Fault (CPF05)*
 
Option Card 
Fault (CPF06)*