37 
 
3.5 Monitoring Parameters U n - □ □
□ □□ □
□ □  
Parameter 
No. 
Name 
LCD Display  
(English) 
Unit  Descriptions 
Un-01  Frequency Command 
Un-01=60.00Hz 
Frequency Command
0.01Hz
Display  frequency  command,  the  displayed  unit 
is determined by Cn-20 
Un-02  Output Frequency 
Un-02=60.00Hz 
Output Frequency 
0.01Hz
Display  output  frequency,  the  displayed  unit  is 
determined by Cn-20 
Un-03  Output Current 
Un-03=12.5A 
Output Current 
0.1A
Display inverter output current 
Un-04  Output Voltage 
Un-04=220.0V 
Output Voltage 
0.1V
Display output voltage command of inverter 
Un-05  Main Circuit DC Voltage
Un-05=310.0V 
DC Voltage 
0.1V
Display DC voltage of inverter main circuit 
Un-06  Output Power 
Un-06=   KW 
Output Power 
0.1KW
Display output power of inverter 
Un-07  Output Power Factor 
Un-07=0.90 
Output P.F. 
0.01  Display output power factor of inverter 
Un-08  Input Terminal Status 
*2
Un-08=00000000 
I/P Term. Status 
- 
 
0
0
0
0
0
0
0
0
0:OPEN 
1:CLOSE 
Input terminal ○
1
 
Input terminal ○
2
 
Input terminal ○
3
 
Input terminal ○
4
 
Input terminal ○
5
 
Input terminal ○
6
 
Input terminal ○
7
 
Input terminal ○
8
 
 
Un-09  Output Terminal Status 
*3
Un-09=00000000 
O/P Term. Status 
- 
 
0
0
0
0
0
0
0
0
0:OPEN 
1:CLOSE 
Relay Contact R2A-
R2C 
Opto-contact D01-
DCOM 
Opto-contact R1A-
R1C 
Reversed 
Reversed 
Reversed 
Reversed 
Reversed 
 
Un-10  S/W Version 
Un-10=00001 
Software Version 
-  -Manufacturing use- 
Un-11  Motor Elapsed Run Hours
Un-11=00001Hr 
Elapsed Time 
1Hr 
Display  total  time  elapsed  after  pressing  RUN 
(display data is 
esettable)*1 
Un-12 
Motor Elapsed Energy 
KWHR 
Un-12=00001Kwh 
Elapsed Energy 
1Kwh
D
isplay total motor output energy (display data is 
esettable)*1