1.5 SPECIFICATIONS
Basic Specifications
220V CLASS
INVERTER (HP)
25 30 40 50 60 75 100
MAX. APPLICABLE MOTOR
OUTPUT HP (KW)*1
25
(18.5)
30
(22)
40
(30)
50
(37
60
(45)
75
(55)
100
(75)
Output
Characteristics
Inverter Capacity
(KVA)
34 41 54 57 67 85 128
Rated Output
Current (A)
80 96 130 160 183 224 300
Max. Output
Frequency
3-Phase, 200/208/220/230V
(Proportional to input voltage)
Rated Output
Frequency
Up to 400Hz available
Power Supply
Rated Input Voltage
And Frequency
3-Phase, 200/208/220V, 50Hz
200/208/220/230V, 60Hz
Allowable Voltage
Fluctuation
+10% ~ -15%
Allowable
Frequency
Fluctuation
±5%
7200GS 440V CLASS
INVERTER (HP) 25
30
40
50
60
75
100
125
150
175
215
250
300
400
500
MAX. APPLICABLE
MOTOR OUTPUT HP
(KW)*1
25
(18.5)
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(132)
215
(160)
250
(185)
300
(220)
400
(300)
500
(375)
Output
Characteristics
Inverter
Capacity (KVA)
34
41
54
68
82
110
138
180
195
230
260
290
385
513
561
Rated Output
Current (A)
40
48
64
80
96
128
165
192
224
270
300
340
450
600
660
Max. Output
Frequency
3-Phase, 380/400/415/440/460V
(Proportional to input voltage)
Rated Output
Frequency
Up to 400Hz available
Power
Supply
Rated Input
Voltage And
Frequency
3-Phase, 380/400/415/440/460V, 50/60Hz
Allowable
Voltage
Fluctuation
+10% ~ -15%
Allowable
Frequency
Fluctuation
±5%
1 Based on 4 pole motor