42
3.7 Order Parameters O n -
Order parameters are already set to the optimum value as initial values, adjustment is not
needed in the normal status.
Function
Parameter
N0.
Name LCD Display (English) Description
Factory
Setting
Control
StatusPI
On-01 Control Status 1
On-01=0000
Control Status 1
XX0Xstored the frequency reference in the
HOLD status (for up/down operation)
XX1XDo not store the frequency reference in
the HOLD status
X0XXPID Feedback zero input protection invalid
X1XXPID Feedback zero input protection valid
0000
On-02 Control Status 2
On-02=0000
Control Status 2
XXX0Inverter overload protection (OL2) valid
XXX1Inverter overload protection (OL2) invalid
XX0XAVR function valid
XX1XAVR function invalid
0XXXOL2&OL5 reset timer 5min valid
1XXXOL2&OL5 reset timer 5min Invalid
0000
On-03 Control Status 3
On-03=0000
Control Status 3
XXX0Anti-hunting gain change depending on
inverter output voltage
XXX1Anti-hunting gain depending on On-07
setting
XX0XTwo-phase PWM modulation
XX1XThree-phase PWM modulation
X0XXPower angle compensation bias change
depending on inverter output frequency
X1XXPower angle compensation bias fixed
0000
On-04
PID control mode
selection
On-04=0000
Reserved
XXX0Bias D control
XXX1Feedback D control
XX0XPID output forward characteristics control
XX1XPID output reversed characteristics control
X0XXFrequency command=PID output
X1XXFrequency command=PID output+
Frequency command
0XXXForward characteristics PID feedback
1XXXReversed characteristics PID feedback
0000
On-05 Not used
On-05=0
Reserved
0.00
On-06 Not used
On-06=0
Reserved
0
Hunting
Prevention
control
On-07
Hunting Prevention
gain
On-07=0.10
Hunt_Prev. Gain
Setting range0.01 ~ 2.55
0.10
On-08
Hunting Prevention
limit
On-08=030%
Hunt_Prev. Limit
Setting range0 ~ 100%
30%
*1
Effective
current
detection
control
On-09
Effective current
detection filter time
constant
On-09=005
I_Det. Time const
Setting range1 (3.5ms) ~ 100 (350ms)
5
*1
(17.5ms)
On-10 Not used
On-10=0
Reserved
0
On-delay
control
On-11 ON-DELAY TIME
On-11=011
ON-Delay Time
Setting range
11 (2.75µs) ~ 160 (40µs), =0.25µs
11
(2.75µs)
On-12
ON-DELAY
Compensated value
On-12=014
ON-Delay Compen.
Setting range0 ~ 160 (40µs), =0.25µs
14
(3.5µs)
On-13 Not used
On-13=0
Reserved
0
On-14 Not used
On-14=0
Reserved
0