43
Function
Parameter
N0.
Name LCD Display (English) Description
Factory
Setting
Energy
Saving
power
detection
On-15
Power detection filter
changing width
On-15=010%
Power_Det. Dead Zone
Setting range:0 ~100%
Setting unit :1%
10%
On-16
Power detection filter time
constant
On-16=020
Power_Det. Time Const.
Setting range:1 ~255
Setting unit :1 (=7ms)
20 (140ms)
Torque
Boost
Control
On-17
Motor phase to phase
resistance
On-17=00.308Ω
Motor Line R
Setting range:0 ~ 65.535Ω
Setting unit :0.001Ω
0.308Ω*
1
On-18
Torque Compensation of care
loss
On-18=425W
Tq. Compens. Care Loss
Setting range:0 ~ 65535W
Setting unit :1W
425W*
1
On-19 Torque Compensation limit
On-19=100V
Tq. Compens. Limit
Setting range:0 ~ 50V*
2
Setting unit :1V
100V*
1
Energy-
saving
Motor
Constant *3
On-20 Motor Constant R1
On-20=00.000Ω
Motor R1
Setting range:0.000 ~ 65.535Ω
Setting unit :0.001Ω
0.000Ω
On-21 Motor Constant R2
On-21=00.000Ω
Motor R2
Setting range:0.000 ~ 65.535Ω
Setting unit :0.001Ω
0.000Ω
On-22 Motor Constant L
On-22=00.000mH
Motor L
Setting range:0.000 ~ 65.535mH
Setting unit :0.001mH
0.000mH
On-23 Motor Constant Rm
On-23=00.000mΩ/ω
Motor Rm
Setting range:0.000 ~ 65.535mΩ/ω
Setting unit :0.001mΩ/ω
0.000mΩ/ω
On-24 Motor Constant Lm
On-24=00.00mH
Motor Lm
Setting range:0.00 ~ 655.35mH
Setting unit :0.01mH
0.00mH
*1. Factory setting differ depending on inverter capacity (Sn-01 set value).
This example shown combination of TECO standard motor 440V, 60Hz, 25HP (18.5KW).
*2. For 220V class, X2 for 440V class.
*3. Setting can be made only when Cn-60=FFH. When the value is changed, K2 (Energy-
saving Coefficient K2) is calculated and the calculated value is set to Cn-58.
Motor constants (On-20 ~On-24) are not stored in NVRAM and become 0 at power startup.
The unit and setting range change depending on the inverter capacity:
1/10 for 220V class 25HP ~ 125HP, 440V class 75HP ~ 500HP.