31 
 
3.4 System Parameters  S n - □ □
□ □□ □
□ □  
Function 
Parameter 
No. 
Name 
LCD Display 
(English) 
Description 
Factory 
Setting
Ref. 
Page
Capacity 
Setting 
Sn-01 
Inverter Capacity 
Selection 
Sn-01=29 
440V 25HP 
Inverter Capacity Selection  *1 
2-32
2-33
V/f Curve  Sn-02  V/f Curve Selection 
Sn-02=2 
V/f Curve 
V/f pattern Selection  2  2-33
Operator Status
Sn-03  Operation Status 
Sn-03=0000 
Operate Setting 
0000:Setting and reading of An-□□, Bn-□
□,Cn-□□, Sn-□□ enabled 
0101:Setting and reading of An-□□, 
Readinng of Bn-□□,Cn-□□, Sn-□
□ enabled 
1110:Contents Initialigation (2-wire)
*2
 
1111:Contents Initialigation (3-wire)
*2
 
1000:Initialize Un-11 contents 
1001:Initialize Un-12 contents 
0000  2-36
eration Mode 
Select 
Sn-04 
Operation Mode Select 
1  
(RUN.STOP 
Selection) 
Sn-04=0011 
Stopping Method 
- - -0:Frequency Command = Control circuit 
terminals VIN or AIN 
- - -1:Frequency Command = Frequency 
Command 1 (An-01) 
- -0 -:RUN.STOP Command = Control 
circuit terminals 
- -1 -:RUN.STOP Command =  
Digital Operator 
00- -:Stopping method = Ramp to stop 
01- -:Stopping method =Coasting  
to stop 
10- -:Stopping method =Full-range DC 
injection branking stop 
11- -:Stopping method = Coasting stop (timer 
function provided) 
0011 
2-37
2-38
2-39
Sn-05 
Operation Mode 
Selection 2  
(I/O terminal function 
selection) 
Sn-05=0000 
I/O Term. Fct. 
- - -0:Stop key effective during operation 
from control terminal 
- - -1:Stop key effective during operation 
from control terminal 
- -0 -:Reverse run enabled 
- -1 -:Reverse run disabled 
- 0- -:Control input terminals ○
1
~○
8
 are 
scanned twice. 
-1- -:Control input terminals ○
1
~○
8
 are 
scanned once. 
0 - - -:Digital operator         key 
= JOG key function 
1- - -:Digital operator       key  
= L/R (Local/Remote) key function 
0000  2-40
Sn-06 
Operation Mode 
Selection 3  
(S-curve and frequency 
reference 
characteristics) 
Sn-06=0000 
S Curve & Cmd. Char.
- -00:S curve=0.2sec 
- -01:S curve=0.0sec (NO S curve) 
- -10:S curve=0.5sec 
- -11:S curve=1.0sec 
-0 - -:Reference command has forward 
characteristics  
(0-10V or 4-20mA/0~100%) 
-1 - -:Reference command has reverse 
characteristics  
(0-10V or 4-20mA/100~0%) 
0- - -:Stop by reference input when 
frequency reference is missing 
1- - -:Operation to continue with 80% of 
frequence reference when frequency 
reference is missing 
0000 
2-41
2-42
2-43
JOG 
(L/R) 
JOG 
(L/R)