EasyManua.ls Logo

TECO SPEECON 7200GS - System Parameters Sn

TECO SPEECON 7200GS
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
3.4 System Parameters S n -
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
Capacity
Setting
Sn-01
Inverter Capacity
Selection
Sn-01=29
440V 25HP
Inverter Capacity Selection *1
2-32
2-33
V/f Curve Sn-02 V/f Curve Selection
Sn-02=2
V/f Curve
V/f pattern Selection 2 2-33
Operator Status
Sn-03 Operation Status
Sn-03=0000
Operate Setting
0000Setting and reading of An-□□, Bn-
,Cn-□□, Sn-□□ enabled
0101Setting and reading of An-□□,
Readinng of Bn-,Cn-□□, Sn-
enabled
1110Contents Initialigation (2-wire)
*2
1111Contents Initialigation (3-wire)
*2
1000Initialize Un-11 contents
1001Initialize Un-12 contents
0000 2-36
eration Mode
Select
Sn-04
Operation Mode Select
1
(RUNSTOP
Selection)
Sn-04=0011
Stopping Method
- - -0Frequency Command = Control circuit
terminals VIN or AIN
- - -1Frequency Command = Frequency
Command 1 (An-01)
- -0 -RUNSTOP Command = Control
circuit terminals
- -1 -RUNSTOP Command =
Digital Operator
00- -Stopping method = Ramp to stop
01- -Stopping method =Coasting
to stop
10- -Stopping method =Full-range DC
injection branking stop
11- -Stopping method = Coasting stop (timer
function provided)
0011
2-37
2-38
2-39
Sn-05
Operation Mode
Selection 2
(I/O terminal function
selection)
Sn-05=0000
I/O Term. Fct.
- - -0Stop key effective during operation
from control terminal
- - -1Stop key effective during operation
from control terminal
- -0 -Reverse run enabled
- -1 -Reverse run disabled
- 0- -Control input terminals
1
~
8
are
scanned twice.
-1- -Control input terminals
1
~
8
are
scanned once.
0 - - -Digital operator key
= JOG key function
1- - -Digital operator key
= L/R (Local/Remote) key function
0000 2-40
Sn-06
Operation Mode
Selection 3
(S-curve and frequency
reference
characteristics)
Sn-06=0000
S Curve & Cmd. Char.
- -00S curve=0.2sec
- -01S curve=0.0sec (NO S curve)
- -10S curve=0.5sec
- -11S curve=1.0sec
-0 - -Reference command has forward
characteristics
(0-10V or 4-20mA/0~100%)
-1 - -Reference command has reverse
characteristics
(0-10V or 4-20mA/100~0%)
0- - -Stop by reference input when
frequency reference is missing
1- - -Operation to continue with 80% of
frequence reference when frequency
reference is missing
0000
2-41
2-42
2-43
JOG
(L/R)
JOG
(L/R)

Related product manuals