EasyManua.ls Logo

TECO SPEECON 7200GS - Page 33

TECO SPEECON 7200GS
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Function
Parameter
No.
Name LCD Display (English) Description
Factory
Setting
Ref. Page
Operation
Mode Select
Sn-07
Operation Mode
Selection 4 (overtorque
detection)
Sn-07=0000
Over Tq. Detect
- - -0Overtorque detection not enabled
- - -1Overtorque detection enabled
- -0 -Enabled only if at agreed frequency
- -1 -Enable during operation (except during
DC injection)
- 0- -Operation continued after overtorque is
detected
- 1- -Coasts to stop if overtorque is detected
0000
2-43
2-44
Sn-08
Operation Mode
Selection 5 (RS-485
communication status
selection)
Sn-08=0011
RS485Comm. Function
- - -0Frequency reference input by RS-485
communication option card (PA-M or
PA-P)
- - -1Frequency reference input by digital
operator or control circuit input terminals
- -0 -RUN/STOP command input by RS-485
Communication option card (PA-M or
PA-P)
- -1 -RUN/STOP command input by digital
operator or control circuit input terminals
0011
2-44
2-45
00- -RS-485 communication fault,
deceleration to stop (Bn-02)
01- -RS-485 communication fault, coast to
stop
10- -RS-485 communication fault,
deceleration to stop (Bn-04)
11- -RS-485 communication fault, continue to
run
Sn-09
Operation Mode
Selection 6 (Energy
saving function
selection)
Sn-09=0000
Eng. Saving Function
- 0- -Energy-saving function ineffective(V/F
Control)
- 1- -Energy-saving function ineffective
0000
2-45
Protective
Characteri-
stic Select 1
Sn-10
Protective
Characteristic
Selection 1
(Stall prevention)
Sn-10=0000
Stall Select
- - -0Stall prevention during acceleration
enabled
- - -1Stall prevention during acceleration not
enabled
- -0 -Stall prevention during acceleration
enabled
- -1 -Stall prevention during acceleration not
enabled
- 0- -Stall prevention during running enabled
- 1- -Stall prevention during running not
enabled
0- - -Decel time during stall
prevention=Bn=02 set value
1- - -Decel time during stall
prevention=Bn=04 set value
0000
2-45
2-46
Protective
Characteri-
stic Select 2
Sn-11
Protective
Characteristic
Selection 2
(Retry and momentary
power failure
protection)
Sn-11=0000
Retry Ride_Thru
- - -0Input phase loss protection function
ineffctive
- - -1Input phase loss protection function
effctive
- -0 -Fault contact is not energized during
Retry operation
- -1 -Fault contact is energized during Retry
operation
-0 - -Operation stopped by momentary power
loss detection (UV1)
-1 - -Operation continues after momentary
power loss
0- - -Output phase loss protection function
ineffctive
1- - -Output phase loss protection function
effctive
0000
2-46
2-47

Related product manuals