33
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
Protective
Characteri-
stic Select 3
Sn-12
Protective
Characteristic
Selection 3 (External
Fault signal function)
Sn-12=0100
External Fault
- - -0:External fault input (terminal ○
3
): NO-
contact input
- - -1:External fault input: NC-contact input
- -0 -:External fault signal: always detected
- -1 -:External fault signal: detected during
running only
00- -:External fault detected: Ramp to a stop
(major fault) by Bn-02 set value
01- -:External fault detected: Coasting to stop
(major fault)
10- -:External fault detected: Ramp to a stop
(major fault) by Bn-04 set value
11- -:External fault detected: opeation to
continue (major fault)
0100 2-47
Control Mode
Select
Sn-13
Control Mode Select
Sn-13=01
V/F Ctrl mode
00:Reserved
01:V/F Control mode
01
2-47
2-48
Protective
Characteri-
stic Select 4
Sn-14
Protective
Characteristic
Selection 5 (Electronic
thermal overload
protection)
Sn-14=0000
Over Load Select
- - -0:Motor overload (OL1) protection
effective
- - -1:Motor overload (OL1) protection
ineffective
- -0 -:Motor overload protection: standard
motor
- -1 -:Motor overload protection: Inverter
duty motor
- 0- -:Motor overload protection time
constants are standard time (8 minutes)
- 1- -:Motor overload protection time
constants are short-time (5 minutes)
0 -- -:Cooling fan run while inverter power
ON
1-- -:Cooling fan run while heat sink
temperature higher then 50℃
0000 2-48
Multi-Function
Select
Sn-15
Terminal ○
5
Function
Sn-15=03
Term.5 Function
00~66
Terminal ○
5
(factory preset for
multi-step speed reference 1)
03
2-49
~
2-58
Sn-16
Terminal ○
6
Function
Sn-16=04
Term.6 Function
00~66
Terminal ○
6
(factory preset for
multi-step speed reference 2)
04
Sn-17
Terminal ○
7
Function
Sn-17=06
Term.7 Function
00~66
Terminal ○
7
(factory preset for jog
frequency reference)
06
Sn-18
Terminal ○
8
Function
Sn-18=08
Term.8 Function
00~66
Terminal ○
8
(factory preset for
external baseblock by NO contact
input)
08
Sn-19
Terminal AUX
Function
Sn-19=00
Multi-Fct Input
00~0C
Terminal AUX (factory preset for
auxiliary frequency command)
00
2-59
2-60
Sn-20
Terminal R2A-R2C
Function
Sn-20=00
Term. R2A Function
00~0F
Terminal R2A-R2C (factory preset
for running)
00
2-63
~
2-64
Sn-21
Terminal D01
Function
Sn-21=01
Term. D01 Function
00~0F
Terminal D01 (factory preset for
zero speed)
01
Sn-22
Terminal R1A
Function
Sn-22=02
Term. R1A Function
00~0F
Terminal R1A (factory preset for
Agreed frequency)
02