34
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
RS-485
commu-
nication
Function
Sn-23 Inverter ststion address
Sn-23=01
Inverter Address
Inverter address can be set as 1~31 01
2-65
Sn-24
RS-485
communication
protocol setting
Sn-24=1000
RS-485 protocol
- -00:No parity
- -01:Even parity parity setting
- -10:Odd parity
- -11:not used
1000
00- -:2400 bps (bit/sec)
01- -:4800 bps baud
10- -:9600 bps rate
11- -:19200 bps setting
Language Sn-25
LCD Language
displayed selection
Sn-25=0
Language select
0:English
1:Chinese
0 2-66
Multi-
Function
Analog Output
Selection
Sn-26
Multi-Function Analog
Output A01 Function
Selection
Sn-26=00
Term. A01 Function
0:Ferquency command (10V/max frequency
command, Cn-02)
1:Output Frequency (10V/max Output
frequency)
2:Output Cueeent (10V/inverter rated
current)
3:Output Voltage (10V/input voltage, Cn-01)
4:DC Voltage (10V/400VDC or 800VDC)
5:Output Power (10V/max. applicable motor
capacity)
6:External analog input command(VIN)
( 10V/10V )
7:External analog input command(AIN)
( 10V/20mA )
8:Multi-function analog input (AUX)
(10V/10V)
9:PID control feedback input (VIN+AIN)
(10V/10V)
A:RS-485
Communication Control
0 2-66
Sn-27
Multi-Function Analog
Output A02 Function
Selection
Sn-27=01
Term. A02 Function
1 2-66
Electronic
Thermal
Overload
Protection
Sn-28
Over Load Select
Sn-28=0
Over Load Select
This function is effective only for 7200GS/GS510 air
compressor inverter models with capacity
40HP(30kW) or larger (230V class), and 75HP
(55kW) or larger (460V class).
- -01: Inverter overload (OL2) protection 103%
continuous, 120% for one minute
- -10: Inverter overload (OL2) protection 103%
continuous, 150% for one minute
- -11: Inverter overload (OL2) protection 113%
continuous, 123% for one minute
Motor over load (OL1) Select (apply to all class)
00- -: Standard motor of 60Hz Overload protection
01- -:
Strengthen the standard motor (F class) of 60Hz
Overload protection
10- -: Standard motor of 50Hz Overload protection
11- -: Strengthen the standard motor (F class) of 50Hz
Overload protection
1010
2-66
2-67
Multi- function
Analog Output
Selection
Sn-29
Pulse Output
Multiplier Selection
Sn-29=0
Pulse Mul.
when multi-function output terminal (DO1) is
set as pulse signal output
0 : 1 F 1 : 6 F 2 : 1 0 F 3 : 1 2 F 4 : 3 6 F
0 2-67