35
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
PA-PID Card
Function
Selection
Sn-30
Pump Operation Mode
Selection
Sn-30=0
Run-Mode Select
0PA-PID Card ineffective
1Fixed inverter driving mode, stop all the
pumps by first-run-last-stop sequence.
2Fixed inverter driving mode, stop the pump
drived by the inverter only.
3Fixed inverter driving mode, stop all the
pumps by first-run-first-stop sequence.
4Cycled inverter driving mode, stop all the
pumps by first-run-first-stop sequence.
5Cycled inverter driving mode, stop the
pump drived by the inverter only.
0 2-68
PA-PID Card
Relay Control
Sn-31
PA-PID Card
Relay 2 Control
Sn-31=0
Invalid
0Relay 2 Invalid
1Relay 2 Valid
0
2-69
Sn-32
PA-PID Card
Relay 3 Control
Sn-32=0
Invalid
0Relay 3 Invalid
1Relay 3 Valid
0
Sn-33
PA-PID Card
Relay 4 Control
Sn-33=0
Invalid
0Relay 4 Invalid
1Relay 4 Valid
0
Sn-34
PA-PID Card
Relay 5 Control
Sn-34=0
Invalid
0Relay 5 Invalid
1Relay 5 Valid
0
Sn-35
PA-PID Card
Relay 6 Control
Sn-35=0
Invalid
0Relay 6 Invalid
1Relay 6 Valid
0
Sn-36
PA-PID Card
Relay 7 Control
Sn-36=0
Invalid
0Relay 7 Invalid
1Relay 7 Valid
0
Sn-37
PA-PID Card
Relay 8 Control
Sn-37=0
Invalid
0Relay 8 Invalid
1Relay 8 Valid
0
Parameter
Copy
Sn-38 Parameter copy
Sn-38=0
Not Loaded
0Not loaded (not copied)
1Upload (from digital operator to inverter)
2Download (from inverter to digital
operator)
3Inspect the EEPROM of digital operator
0
2-69
2-70
Sn-39 Not Used
Sn-39=0
Reserved
0Invalid
0