ANALOG CONTROL
139
Remote Monitoring
The 2260B power supplies have remote monitoring support for
current and voltage output. They also support monitoring of
operation and alarm status.
External monitoring of output voltage and current → from page
139
External monitoring of operation mode and alarm status → from
page 141
External Voltage and Current Monitoring
Background
The MIL 26 pin connector is used to monitor
the current (IMON) or voltage (VMON) output.
An output of 0~10V represents the voltage or
current output of 0~ rated current/voltage
output.
IMON = (current output/full scale) × 10
VMON = (voltage output/full scale) × 10
External voltage and current monitoring
doesn’t need to be enabled in the configuration
settings.