CA60Plus control panel Installation manual 23
ADDRESS 47 220 V AC POWER SUPPLY FAILURE INDICATION DELAY
AC DELAY NO Disables 30 minutes indication delay for 220 V power supply failure in
keyboards and message transmission via digital communicator.
Light-emitting diodes 1 to 6 do not light up.
YES Enables 30 minutes delay indication for 220 V power supply failure in
keyboards and message transmission via digital communicator.
Light-emitting diodes 1 to 6 light up.
DEFAULT : NO
ADDRESS 46 TELEPHONE LINE FAILURE INDICATION DELAY
LF DELAY A delay of 0 to 99 minutes is set prior to indication of a telephone line failure
(ММ). The indication has a hexadecimal expression. Two digits are entered.
When a period is less than 10 minutes the first digit introduced must be
0. If no indication of a dead telephone line is needed, 00 is entered.
DEFAULT : 00 minutes
ADDRESS 48 FIRE SIGNAL DURATION
The duration of the alarm signal for a FIRE event is selected at this address.
Programming this address affects the performance of the programmable SIREN
output.
Every click of a digital button alternatively changes the type of duration of the
sound signal. The display indication is shown in the table.
ENABLED The FIRE signal duration is set at address 42 BELL TIME. The 1 to 6 LEDs
light up.
DISABLED There is a FIRE alarm signal until a valid system user or master user code is
introduced. The 1 to 6 LEDs do not light up.
DEFAULT : DISABLED
ADDRESS 49 TAMPER ALARM SIGNAL
A sound alarm signal is enabled or disabled at this address for a TAMPER
event when the system is not armed. Programming this address will not affect
the TAMPER signal when the system is in armed mode. Programming this
address will affect the performance of the programmable SIREN output.
Every click of a digital button alternatively changes the enabled / disabled
status. The display indication is shown in the table.
ENABLED Enabled sound alarm signal for TAMPER event, when the system is not armed.
The 1 to 6 LEDs light up.
DISABLED Disabled sound alarm signal for TAMPER event, when the system is not armed.
A TAMPER event is indicated by an interrupted sound signal emitted by the
system keyboard. The 1 to 6 LEDs do not light up.
DEFAULT : ENABLED