Installation and Programming Manual - СА62 Alarm Control Panel 61
240 Manager code 3 (0000) Enter 4 or 6 digit code (depends on the settings at ADDRESS 1001 from the Engineering Menu) (- - - -) (- - - -) (- - - -)
241 Manager code 3 Attributes 5. Part A 6. Part B
242 Proximity card Register Put the card close to the proximity reader.
243 Proximity card Delete Press ENTER button to delete the card.
300 Display LOG Memory LOG memory le review.
400 CHIME Enable NO - LEDs off YES - LEDs on NO NO NO
500 BYPASS ZONES
Press a number of a ZONE which you want to bypass.
Use buttons 1 - 9 and combinations ARM+0 (Zone 10), ARM+1 (Zone 11) and ARM+2 (Zone 12),
600 Setting the clock Clock setting ( HH:MM). Settings at RESET → 00:00. 00:00 00:00 00:00
601 Setting the date Date setting ( DD:MM). Settings at RESET01:01. 01:01 01:01 01:01
SUPPLEMENT A - Default Programming Tables
TABLE 3: User Menu - DEFAULT CONFIGURATION 0, 1, 2 and 3
ADDRESS MENU
DEFAULT CONFIGURATION 0
DEFAULT
CONFIG. 1
DEFAULT
CONFIG. 2
DEFAULT
CONFIG. 3
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
0 Change own code (- - - -) Enter 4 or 6 digit code (depends on the settings at ADDRESS 1001 from the Engineering Menu) (1111) (1111) (1111)
1 Display LOG Memory LOG memory le review.
2 CHIME Enable NO - LEDs off YES - LEDs on NO NO NO
3 BYPASS ZONES
Press a number of a ZONE which you want to bypass.
Use buttons 1 - 9 and combinations ARM+0 (Zone 10), ARM+1 (Zone 11) and ARM+2 (Zone 12),
(- - - -) means, that there is no default programmed user / manager code combination
Note: Table 3 contains the default settings for User programming menu entered with User Code 1.
- Default settings at hardware or software RESET. The default CONFIGURATION 0 is set by default.