TEXA INDUSTRIES S.r.l. - Strada Ca’ Bruciata,5 46020 Pegognaga (MN) ITALY - Tel. +39 0376 554511 - Fax +39 0376 558606 www.texaindustries.com
TX-i40
C17000905R00
(IT) Manuale d’istruzioni controllore a microprocessore
(GB)
Microcontroller instruction manual
(DE)
Benutzerhandbuch Mikroprozessor gesteuerter Kühlstellenregler
(FR)
Microcontrôleur - Mode d’emploi
(ES) Manual de instrucciones del controlador con microprocesador
(IT) Condizionatori per armadi elettrici
(GB) Cooling units for electric enclosures
(DE) Kühlgeräte fur Schaltschränke
(FR) Climatiseurs pour armoires électriques
(ES) Climatizadores para armarios électricos

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the TEXA TX-i40 and is the answer not in the manual?

Summary

General Warnings and Safety Instructions

WARNING - Do Not Misuse Regulator

Do not use the regulator for functions other than those described; do not use it as a safety device.

CAUTION - Check Application Limits

Check the limits of application.

CAUTION - Isolate Power Before Maintenance

Isolate the power to the device before commencing any maintenance work.

NOTICE - Report Faults Immediately

Contact TEXA INDUSTRIES S.r.l. immediately in writing in the event of faults or malfunctions.

General Information on TX-i40

TX-i40 Display Description

Describes the TX-i40 display layout and its components.

Dimensions and Installation

Illustrates the dimensions and panel mounting requirements for the TX-i40.

User Interface Overview

Keypad Functions

Details the functions of each key on the device's keypad.

Testing Sequence from Keypad

Explains the procedure to activate and execute the keypad testing sequence.

Display Icons and Meaning

Illustrates the icons on the TX-i40 display and explains their meanings.

Menu Navigation and Structure

Accessibility Levels

Describes the three access levels (User, Installer, Manufacturer) for menu navigation.

Menu Access Procedure

Explains how to access and navigate through the device menus.

List of Available Menus

Lists the available menus (SEt, ALM, PAr, OHr, His, nFo, PSS, CoL) and their functions.

PAr Menu Parameter Grouping

Details the grouping and identifying labels for parameters within the PAr menu.

OHr Menu Component Hours

Explains the components and their hours of operation displayed in the OHr menu.

Electronic Board Components

LED Indicators Layout and Meaning

Illustrates the layout of LED indicators on the electronic board and their meanings.

I;O Connections Overview

Details the meaning and function of all I/O connectors on the electronic board.

Regulation Settings and Parameters

Temperature Regulation Explained

Explains how the compressor relay maintains the set temperature with hysteresis.

Evaporator Fan Management

Defines parameter P01 for evaporator fan operating modes, including Energy Saving.

Energy Saving Regulation Mode

Describes the conditions and operation of the evaporator fan in Energy Saving mode.

Automatic Units Conversion

Explains how to convert temperature and pressure units using parameter G07.

Restoring Default Parameters

Describes how to restore default parameters at the installer level.

Two Unit Sequencing Connection

Details connecting two units in sequence using a dedicated cable and parameter G20.

Generic Alarm Behaviour

Explains unit behavior following a generic alarm based on parameter A85.

Alarm Relay Behaviour

Describes how the alarm relay responds to fault conditions based on parameter A84.

Alarms Overview and High Temp

Introduces the low/high regulation temperature alarms and parameter A86.

Low Regulation Temperature Alarm

Details the threshold and cancellation for Low Regulation Temperature alarm (Lrt).

Filter Maintenance Warning

Explains the filter maintenance warning (HFI) and how to reset it.

Maximum Pressure Alarm (HP1)

Describes the Maximum Pressure alarm (HP1) and its automatic/manual reset.

Minimum Pressure Alarm (HP1)

Describes the Minimum Pressure alarm (HP1) and its automatic/manual reset.

Phase Sequence Alarm (PH)

Explains the Phase Sequence alarm (PH) and how to resolve it.

High Condensation Pressure Alarm

Details the High Condensation Pressure alarm (HP) and its warning conditions.

Low Condensation Pressure Alarm

Details the Low Condensation Pressure alarm (LP) and its warning conditions.

High External Temperature Alarm

Details the High External Temperature alarm (HtO) and its warning conditions.

Low External Temperature Alarm

Details the Low External Temperature alarm (LtO) and its warning conditions.

Manual Alarms Reset Procedure

Explains the procedure to disable manual reset alarms.

TEXA TX-i40 Specifications

General IconGeneral
CoreARM Cortex-M4
ADC Resolution12-bit
DAC Resolution12-bit
Operating Temperature-40°C to +85°C
Flash Memory512 KB
Communication InterfacesUSB, UART, SPI, I2C, CAN