EasyManua.ls Logo

TEXIO PU6-200 - 9 Maintenance; Introduction; Units under Warranty; Periodic Maintenance

TEXIO PU6-200
81 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
8. MAINTENANCE
8.1. INTRODUCTION
This chapter provides information about maintenance, calibration and troubleshooting.
8.2. UNITS UNDER WARRANTY
Units requiring repair during the warranty period should be returned to a Lambda authorized service
facility. Refer to the addresses listing on the back cover of this manual. Unauthorized repairs
performed by other than the authorized service facilities may void the warranty.
8.3. PERIODIC MAINTENANCE
No routine maintenance of the power supply is required except for periodic cleaning. To clean,
disconnect the unit from the AC supply and allow 30sec. for discharging internal voltage. The front
panel and the metal surfaces should be cleaned using mild solution of detergent and water. The
solution should be applied onto a soft cloth, and not directly to the surface of the unit. Do not use
aromatic hydrocarbons or chlorinated solvents for cleaning. Use low pressure compressed air to
blow dust from the unit.
8.4. ADJUSTMENTS AND CALIBRATION
No internal adjustment or calibration is required. There is NO REASON to open the power supply
cover.
8.5. PARTS REPLACEMENT AND REPAIRS
As repairs are made only by the manufacturer or by authorized service facilities, no parts
replacement information is provided in the manual. In case of failure, unusual or erratic operation of
the unit, contact a Lambda sales or service facility nearest you. Please refer to the Lambda sales
offices addresses listing on the back cover of this user manual.
8.6. TROUBLESHOOTING
If the power supply appears to operating improperly, use the troubleshooting guide to determine
whether the power supply, load or external control circuit are the cause.
Configure the power supply for basic front panel operation and perform the tests of section 3.8 to
determine if the problem is with the supply.
Table 9-1 provides the basic checks that can be performed to diagnose problems, and references
to sections of this manual for further information.
Table 9-1: Troubleshooting guide
SYMPTOM CHECK ACTION REF.
Is the AC power cord
defective?
Check continuity, replace if
necessary.
3.7
No output. All displays and
indicators are blank.
Is the AC input voltage
within range?
Check input AC voltage.
Connect to appropriate
voltage source.
3.6
3.7
Output is present momentarily
but shuts off quickly.
The display indicates “AC”.
Does the AC source voltage
sag when load is applied?
Check input AC voltage.
Connect to appropriate
voltage source.
3.6

Table of Contents