Before using this function for the first time, please set the local time in parameter items 54, 55, then
the user can set the corresponding time slot according to the local peak and valley tariff charges.
6.5 Battery parameter
Li-ion battery
Parameter/Battery type
LFP
User-
defined
L16
L15
L14
USER
Over-voltage cut-off
voltage
60V
60V
60V
60v
Equalization charging
voltage
-
-
-
40~60V
settable
Bulk charging voltage
56.8V
53.2V
49.2V
40~60V
settable
Float charging voltage
56.8V
53.2V
49.2V
40~60V
settable
Under-voltage alarm
voltage
49.6V
46.4V
43.2V
40~60V
settable
Under-voltage cut-off
voltage
48.8V
45.6V
42V
40~60V
settable
With 3 definable periods, the user can freely set the
mains charging/carrying time within the range of
00:00 to 23:59. During the time period set by the
user, if PV energy is available, PV energy will be used
first, and if PV energy is not available or insufficient,
utility energy will be used as a supplement.
With 3 definable time periods, users can freely
set the battery discharge time within the range
of 00:00 to 23:59. During the time period set by
the user, the inverter will give priority to the
battery inverter to carry the load, and if the
battery power is insufficient, the inverter will
automatically switch to mains power to ensure
stable operation of the load.