MP-3000 Controller
83
F1.07
Injection Valve Test
Activated
7.6 A 7.5 A 7.6 A
Condenser fan and compressor remain
on. Liquid injection valve is turned on.
Amp draw is measured and verified to be
a minimum of 0.1 amps higher that test
F1.06.
NOTE: If the condenser fan is off
for test F1.06, the fan remains off
for this test.
29, 31 10 Seconds
F1.08
Low Pressure Test
Activated
0.8 A 0.7 A 0.8 A
Condenser fan, compressor and liquid
injection valve remain on. Stepper valve
is closed and low pressure cutout is
verified to open.
NOTE: If the condenser fan is off
for test F1.06, the fan remains off
for this test.
31 10 Seconds
F1.09
Warm Gas Bypass
Valve Activated
8.3 A 8.2 A 8.3 A
With condenser fan and compressor on,
compressor is operated at 25% capacity.
Liquid injection valve is off. Bypass valve
is turned on. Amp draw measured and
verified to be a minimum of 0.2 amps
higher that test F1.06.
NOTE: If the condenser fan is off
for test F1.06, the fan remains off
for this test.
F1.10
Heat Test
Activated
5.2 A 5.1 A 5.2 A
Amp draw is measured and compared to
voltage:
• 4.4 Amps approx. at 400V
• 5.1 Amps approx. at 460V
10, 11 10 Seconds
F1.11
Humidify Valve Test
Activated
0.1 A 0.0 A 0.1 A
Coil/Dehumidify valve is turned on for
2 seconds, off for 2 seconds and on for 2
seconds to verify valve operation.
Function test log ends.
Alarms (if any) are cleared from
datalogger. However, alarms (if any)
remain in alarm list as not active until
acknowledged.
None 6 Seconds
CSR & Function Test Procedure (Continued)
LED
Display
(Test No.)
LCD Display
(Shows Approx. Amps for
460V, 60 Hz Unit)
Test Description
Possible
Alarms
Duration
(Time)