Page 5-14 Document Ref 947571-001 Rev 2
Installation Quantium 110 & 210 Installation Manual
WWC - Single Phase Suction
2) Make the connections according to the correct wiring diagram shown in this
section.
IMPORTANT :- ENSURE THE CORRECT WIRING DIAGRAM IS
FOLLOWED.
3) When complete, ensure that all tools and unused materials are removed, close
the calculator door and lock.
4) Re-instate power to the dispenser and test its operation.
PE N L1
FORECOURT
WIRING
TERMINALS IN
CALC HEAD
KIOSK
EQUIPMENT
3x2.5mm²
cable or MICC
* Note 1
Motor MCB
* Note 1
16A Motor Circuit Breaker for
models with 2 x TQP : Q200T 2-2
models
10A Motor Circuit Breaker for all
other models
** Note 2
WWC
Registers
MOTOR
POWER
Calc** MCB
2A
FUSE
CALC**
POWER
L L
Lights MCB
5x1.5mm² cable
or
4x1.0mm² MICC
2A
N PEN PE
FUSE
LIGHTS
POWER