HX7+ ASD Installation and Operation Manual 5
Conductor Routing and Grounding 
Precautions
• Use separate metal conduits for routing the input power, output power, and control circuits.
• A separate ground cable should be run inside the conduit with the input power, output power, and 
control circuits.
• DO NOT connect CC to earth ground.
•Use the CC terminal as the return for analog input terminals VI, RX, and RR.
•Use the CC terminal as the return for output terminals FP, PP, and P24.
• Use the negative terminal of the AM, FM, and II terminals as the return for these analog inputs.
• Always ground the unit to prevent electrical shock and to help reduce electrical noise.
• If the ASD is being used in an ungrounded system (floating system) or in an unsymmetrically 
grounded system, the EMI filter must be disconnected or removed. The ASD may be damaged if 
the EMI filter is used under either of these conditions.
• It is the responsibility of the ASD installer/maintenance personnel to provide proper grounding and 
branch circuit protection in accordance with the NEC and any applicable local codes.
— The Metal Conduit Is Not An Acceptable Ground —
Power Connections Precautions
CONTACT WITH ENERGIZED WIRING WILL CAUSE 
SEVERE INJURY OR LOSS OF LIFE.
• Turn off and lock-out/tag-out all power sources before proceeding to connect the power wiring to 
the equipment.
• Ensure that all power sources are turned off and isolated in accordance with established lock-out/
tag-out procedures before connecting the 3-phase power source wiring to the ASD input terminals 
and connect the ASD output terminals to a motor of the correct voltage and type for the application 
(refer to the NEC Article 300 – Wiring Methods and Article 310 – Conductors For General 
Wiring). Size the branch circuit conductors in accordance with the NEC Table 310.16.
• Ensure that the 3-phase input power is NOT connected to the output of the ASD. This will damage 
the ASD and may cause injury to personnel.
• If multiple conductors are used in parallel for the input or output power and it is necessary to use 
separate conduits, each parallel set shall have its own conduit and not share its conduit with other 
parallel sets (i.e., place U1, V1, W1, and a ground wire in one conduit and U2, V2, W2 and a 
ground wire in another; refer to the NEC Article 300.20 and Article 310.4). National and local 
electrical codes should be referenced if three or more power conductors are run in the same conduit 
(refer to the NEC Article 310 adjustment factors).
Note: National and local codes should be referenced when running more than three 
conductors in the same conduit.
• Ensure the correct phase sequence and the desired direction of motor rotation in the Bypass mode 
(if applicable).