42 HX7+ ASD Installation and Operation Manual
Keypad Installation Precautions
Install the unit securely in a well ventilated area that is out of direct sunlight using the four mounting holes
of the keypad. The ambient temperature rating for the keypad is 14 to 104° F (-10 to 40° C).
• Select a mounting location that is easily accessible by the user.
• Avoid installation in areas where vibration, heat, humidity, dust, metal particles, or high levels of
electrical noise (EMI) are present.
• Do not install the keypad where it may be exposed to flammable chemicals or gases, water, solvents,
or other fluids.
• Turn the power on only after securing all enclosure covers and/or closing the door of the ASD.
Keypad Remote Mounting w/o the ASD-MTG-KIT
Note: See Figure 22 for the dimensions and the item locations referenced in steps 3 through 5.
1. At the keypad mounting location, identify and mark the location of the 3.80” by 3.29” hole and the
0.22” screw holes.
2. Cut the 3.80” by 3.29” rectangular hole.
3. Drill the four 0.22” screw holes.
4. Attach and secure the keypad to the front side of the mounting location using the four 6-32 x 5/16”
pan head screws, the #6 split lock washers, and the #6 flat washers.
5. Connect the RJ-45 extension cable(s).
Keypad Dimensions (mounting)
Figure 22. Keypad Mounting Dimensions (inch/mm).