HX7+ ASD Installation and Operation Manual
11
CE Compliance Requirements
In Europe, the EMC Directive and Low-Voltage Directive requires that the CE mark be placed on the 
product as an indication of compliance to these directives.
The ASD is designed to be installed in an enclosure and is used in conjunction with other machines or 
systems. Because the ASD does not function alone, it is not subject to the EMC Directive.
However, because the ASD is subjected to the Low-Voltage Directive, the CE mark must be placed on 
all ASDs.
The CE mark must be placed on all machines and systems with a built-in ASD because the machines 
and systems are subject to the above directives.
If the ASD is the final product, it may also be subject to machine-related directives. When required, it is 
the responsibility of Toshiba International Corporation to place the CE mark on qualifying ASDs.
The CE Compliance section provides installation information and other required measures to satisfy the 
EMC Directive and the Low-Voltage Directive.
Toshiba International Corporation has tested representative ASD models that were installed as 
described in this manual to ensure compliance with the EMC Directive. Because system compliance is a 
function of the installation and connectivity, not all ASDs can be tested for EMC Directive compliance.
Applicable EMC standards vary depending on the composition of the enclosure in which the ASD is 
installed, the relationship with other electrical devices installed in the enclosure, wiring conditions, 
equipment layout, etc. To that end, ensure that your machine or system complies with the EMC 
standards as a whole.
Toshiba International Corporation has applied the following standards for systems deployed in the 
European market.
Table 1. European Market Standards.
Category Subcategory Product Standards Test Standard and Level
Emission
Radiated
EN 61800-3
EN55011 Class A Group 1
Conducted EN55011 Class A Group 1
Immunity
Generic Industrial EN 61000-6-2
Electrostatic Discharge EN 61000-4-2
Radiated EN 61000-4-3
Electrical Fast Transient Burst EN 61000-4-4
Lightning Surge EN 61000-4-5
Conducted EN 61000-4-6
Voltage Dip EN 61000-4-11
Generic Standards EN 61000-6-4
Adjustable Speed Electronic Power Drive Systems EN 61800-5-1