44 HX7+ ASD Installation and Operation Manual
System Operation
Startup Wizard
Upon initial system powerup, the Startup Wizard may be run to assist the user with the initial
configuration of the input power settings and the output parameters of the HX7+ ASD. The HX7+ ASD
may also be setup by directly accessing each of the individual parameters (see the section titled
Direct
Access Parameter Information on pg. 72). See the section titled Default Setting Changes on pg. 45 for
more information on changing the parameter settings.
The Startup Wizard is run from the Program (menu) Startup Wizard.
The Startup Wizard querys the user for the following information:
Note: After each entry, Finish may be clicked to load the Startup Wizard settings and exit.
1. Run now? (if selected continue on to step #2)/Run next time at power up? (if selected go to
Program screen)/Manually configure? (if selected click Finish
Frequency Command screen).
2. The Voltage and Frequency Rating of the Motor.
3. The Upper Limit Frequency.
4. The Lower Limit Frequency.
5. Adjust Accel/Decel Automatically? (if Ye s, continue from step 8).
6. The Acceleration Time.
7. The Deceleration Time.
8. The Volts Per Hertz Setting.
9. The Motor Current Rating.
10. The Command Source.
11. The Frequency Command Source.
Click Finish to load the settings of the Startup Wizard into the ASD. Further application-specific
settings may be required.
See the section titled Startup Wizard Requirements on pg. 53 for additional information on the Startup
Wizard.
Operation (Local)
Note: See F003 for information on Remote operation.
To turn the motor on, perform the following:
1. Press the MON/PRG key until the
Frequency Command screen is
displayed.
2. Press the Local|Remote key to enter the
Local mode (green Local|Remote LED
illuminates).
3. Turn the Rotary Encoder clockwise
until the Frequency Command value is
at the desired setting.
Frequency
Command