HX7+ ASD Installation and Operation Manual 55
7. Command Source
This selection establishes the source of the Run commands (e.g., F, R, Stop, etc.).
Settings:
0 — Terminal Board
1 — CN8 Option (LED Keypad)
2 — TTL
3 — RS232/RS485
4 — Communication Card
8. Frequency Command Source
This selection establishes the source of the Frequency (speed) command.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — CN8 Option (LED Keypad)
6 — Binary/BCD Input
7 — TTL
8 — RS232/RS485
9 — Communication Card
10 — UP/DOWN Frequency
11 — Pulse Input (option)
9. Wizard Finished!
This screen is the final screen of the Startup
Wizard. The basic parameters of the HX7+ ASD
have been set. Click Exit to load the Startup
Wizard input and to return to the Frequency
Command screen. Additional application-specific
programming may be required.