150 HX7+ ASD Installation and Operation Manual
VI/II Gain Adjust
Program Frequency Setting Speed Reference Setpoints VI/II
This parameter is used to fine tune the gain of the VI/II input terminals.
Note: See note on pg. 57 for further information on the VI/II terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type — Numerical
Factory Default 50
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 255
RR Bias Adjust
Program Frequency Setting Speed Reference Setpoints RR
This parameter is used to fine tune the bias of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide an output of zero from the ASD.
Direct Access Number — F472
Parameter Type — Numerical
Factory Default 120
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 255
RR Gain Adjust
Program Frequency Setting Speed Reference Setpoints RR
This parameter is used to fine tune the gain of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F473
Parameter Type — Numerical
Factory Default 61
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 255
RX Bias Adjust
Program Frequency Setting Speed Reference Setpoints RX
This parameter is used to fine tune the bias of the RX input terminal when this
terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide an output of zero from the ASD.
Direct Access Number — F474
Parameter Type — Numerical
Factory Default 99
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 255
F471 F474