172 HX7+ ASD Installation and Operation Manual
Cumulative Run Timer Alarm Setting
Program Protection Cumulative Run Timer
This parameter sets a run-time value that, once exceeded, closes a contact. The
output signal may be used to control external equipment or used to engage a
brake.
Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Direct Access Number — F621
Parameter Type — Numerical
Factory Default 175.0
Changeable During Run — Ye s
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 100)
Abnormal Speed Detection Filter Time
Program Protection Abnormal Speed
This parameter sets the time that an over-speed condition must exist to cause a
trip.
Direct Access Number — F622
Parameter Type — Numerical
Factory Default 10.0
Changeable During Run — No
Minimum — 0.01
Maximum — 100.0
Units — Seconds
Over-Speed Detection Frequency Range
Program Protection Abnormal Speed
This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Overspeed Detected alert.
Direct Access Number — F623
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 30.0
Units — Hz
Speed Drop Detection Frequency Range
Program Protection Abnormal Speed
This parameter sets the lower level of the Base Frequency range that, once
exceeded, will cause a Speed Drop Detected alert.
Direct Access Number — F624
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 30.00
Units — Hz
Over-Voltage Stall Level (fast)
Program Protection Stall
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Over-Voltage Stall. An Over-Voltage Stall increases the output
frequency of the drive during deceleration for a specified time in an attempt to
prevent an Over-Voltage Trip.
If the over-voltage condition persists for over 250 µS, an Over-Voltage Trip
will be incurred.
Note: This feature may increase deceleration times.
Direct Access Number — F625
Parameter Type — Numerical
Factory Default — (ASD dependent)
Changeable During Run — Ye s
Minimum — 50.00
Maximum — 250.0
Units — %