Unified Controller nv Series type1 light PROFIBUS-DP module PF611A / PF612A User’s Guide
11
Mode 1 setup switch (decimal rotary switch)
Mode 2 setup switch (4 binary DIP switch)
Mode 1 and 2 setup switch are used for the following settings.
Table 2-3 Mode 1 and 2 setup switch
MD6
MD7
MODE1
I/O byte(word) count
OFF
OFF
1
IN/OUT
2Byte(1Word)
OFF
OFF
2
IN/OUT
4Byte(2Word)
OFF
OFF
3
IN/OUT
8Byte(4Word)
OFF
OFF
4
IN/OUT
16Byte(8Word)
OFF
OFF
5
IN/OUT
32Byte(16Word)
OFF
OFF
6
IN/OUT
64Byte(32Word)
OFF
OFF
7
IN/OUT
128Byte(64Word)
OFF
OFF
8
IN/OUT
208Byte(104Word)
MD6
MD7
MODE1
Input byte(word) count
ON
OFF
1
INPUT
2Byte(1Word)
ON
OFF
2
INPUT
4Byte(2Word)
ON
OFF
3
INPUT
8Byte(4Word)
ON
OFF
4
INPUT
16Byte(8Word)
ON
OFF
5
INPUT
32Byte(16Word)
ON
OFF
6
INPUT
64Byte(32Word)
ON
OFF
7
INPUT
128Byte(64Word)
ON
OFF
8
INPUT
244Byte(122Word)
MD6
MD7
MODE1
Output byte(word) count
OFF
ON
1
OUTPUT
2Byte(1Word)
OFF
ON
2
OUTPUT
4Byte(2Word)
OFF
ON
3
OUTPUT
8Byte(4Word)
OFF
ON
4
OUTPUT
16Byte(8Word)
OFF
ON
5
OUTPUT
32Byte(16Word)
OFF
ON
6
OUTPUT
64Byte(32Word)
OFF
ON
7
OUTPUT
128Byte(64Word)
OFF
ON
8
OUTPUT
244Byte(122Word)
Any setting other than the above will cause the module to fail.
MD6
MD7
MODE1
I/O byte(word) count
ON
ON
-
This setting is not available.
It will cause the module to fail.
Turn off the power when operating the mode 1 setup switch.
The registered setting of the Mode 1 setup switch and the input/output data size of NetTool
should be the same. If they do not match, an error will occur due to the consistency check.
Set the same
number of words
for transmit and
receive
Set only receive words
count
Set only transmit words
count