Chapter 3 Connecting Devices
6F8C1575
40
■ Wiring the power module of the type2 light controller
Figure 3-2 Wiring power module PS693
*1: Line filter ground (LG)
Normally, the LG or FG terminal is shorted
for grounding, but the LG terminal can be
opened or a dedicated ground wiring
provided depending on the grounding
condition (e.g. the presence of leak current
or separately provided power ground).
*2: Frame ground (FG)
The FG is connected to the unit chassis.
For details, refer to “1.7 Grounding the Controller.”
Note
・
The terminal screw size is M3.5. Use a crimping terminal of 7 mm or less in width for this
size of screws.
フェライトコア
2 ターン
24V output
3.3V/5V and 24V
output should be
RUN
contact
Input power
100-240VAC
5000pForless
5000pForless