Chapter 1 On Installing type2 light Controllers
6F8C1575
8
1.4 Part Names and Functions of Power Module
Part names and functions of power module PS693 are described.
Use it with the terminal block cover while it is live.
Never touch the terminal.
Failure to do so may cause an electric shock.
Precautions for using the power module
・
This power module is dedicated to unified controller nv series
type1 and type2 controllers. Do not use it independently for any
other purposes.
・
Take at least one second from power-off to subsequent
power-on, otherwise, the module may not start properly or
malfunction.
・
If the power supply is cut off due to an output error (e.g.
overcurrent), turn off the power, remove the cause of error, and
turn on the power again. Take at least 40 seconds to turn on the
power again; otherwise, the module may not start properly.
Figure 1-3 Power module PS693 front panel (without terminal block cover)
CAUTION
Mandatory
①
POWER LED
②
External power terminal (24VDC)
③
RUN contact
④
Power supply (100-240VAC)
⑥
Frame ground terminal
⑤
Line filter ground terminal
Prohibited
WARNING