Chapter 3 Connecting Devices
6F8C1575
42
3.2 Connection of TC-net I/O Loop Cable
Connect the TC-net I/O loop cable to the TC-net I/O loop connector (RJ45) of the controller
module.
Connecting the TC-net I/O loop cable
Connect the controller unit and TC-net I/O nodes by connecting LP2 and LP1 with the
TC-net I/O loop cable in order from the smallest node number.
Please wire the TC-net I/O loop cable under maximum length. About the maximum
length, the whole loop in 100m, 10m between next two nodes.
Single configuration
Figure 3-4 Connection of TC-net I/O loop cable (single configuration)
To TC-net I/O connector LP2 of TC-net I/O adapter
To TC-net I/O connector LP1 of TC-net I/O adapter
TC-net I/O loop cable
PUM
21
LP1
LP2
1
SA91
1
LP1
LP2
3
SA91
1
LP1
LP2
4
SA91
1
LP1
LP2
16
Node No.
RUN
HALT
PRUN
TRUN
HLTH
RUN
ONL
STBY
HALT
ERR
ALM
BATT
TRK
LP
SCAN
EN-B
LP-1
LP-2
EN-A
ACT
-1
ACT
-A
ACT
-2
ACT
-B
LNK
-1
LNK
-2
LNK
-A
LN
K-B