EasyManuals Logo

Toshiba TOSVERT VF-AS1 Series User Manual

Toshiba TOSVERT VF-AS1 Series
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
E6581581
- 12 -
-At I/O scanning and connected communication
The time until time-out operates =
RPI42
Connection Timeout Multiplier
+ f850 (disconnection detection
extended time)[0.1s]
RPI: Request Packet Interval
-At Unconnected communication
Time-out is not operating.
[f851: Operation at communication error by disconnection]
The range 0: Inverter stop, communication command, frequency mode open (by
cmod, fmod)
1: None (continued operation)
2: Deceleration stop
3: Coast stop
4: Network error (err8 trip)
5: Preset speed operation (by f852 setting)
The operation of the inverter when the communication fault occurs can
be specified.
[f852: Preset speed operation selection]
The range 0: None
1 to 15: Preset speed
The operation frequency of the inverter when the communication fault
occurs can be specified. (Only when f851 is set to 5)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 Series and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Series Specifications

General IconGeneral
CategoryInverter
Input Frequency50/60 Hz ±5%
SeriesVF-AS1
Overload Capacity150% for 60 seconds
Input Voltage3-phase 200 to 240 VAC
Protection DegreeIP20
Ambient Temperature-10 to +50 °C (14 to 122°F) (Open type)
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Ground Fault
Braking UnitBuilt-in
CommunicationRS485
Power Range0.4 to 110 kW
Cooling MethodForced Air Cooling
Operating Temperature-10 to +50 °C (14 to 122°F) (Open type)
AltitudeUp to 1000 m
Output Voltage3-phase, voltage corresponding to input voltage

Related product manuals