EasyManua.ls Logo

Toshiba TOSVERT VF-AS1 Series - FA06 Command Word 1

Toshiba TOSVERT VF-AS1 Series
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581581
- 13 -
3.2.4. Command data (f831-f838), Monitor data (f841-f848)
The outline is indicated about the setting item of parameter f831 - f838 and
f841 - f848 in Instance 102/152 and 103/104 of use. Please refer to a
communication functional description (VF-AS1: E6581315/VF-PS1: E6581413) for
details.
3.2.4.1. How to use Instance 102/152 and 103/104
Instance 102/152 and 103/104 choose a command or the monitor of the driving state by a menu of f831 -
f838 and f841 - f848 and can perform the communication that is cyclic of EtherNet/IP™.
Example 1: Command transmitting by output Instance 102
When it runs by EtherNet/IP™ communication and wants to order you, please choose parameter FA06 (a
communication option command) for command data (f831=1 (FA06)).
For example, please set 0xC400 in FA06 when you want to send the command from an EtherNet/IP™
option and the availability of the frequency order and a driving order. (Please refer to next page)
Example 2: State monitoring by the input instance 152.
When you want to monitor the output current, set “3 (FD03)” to parameter f841.
The value of the parameter
FD03 specified as 0 and 1 byte of the input instance 152 with the parameter
f841 is inputted.
VF-AS1/PS1
IPE001Z
"0xC400" is set as parameter FA06
Byte Value
0 00
1 C4
2 ...
3 ...
... ...
EtherNet/IP Master
Parameter Value
f831 1 (FA06)
f832 ...
f833 ...
... ...
Output Instance102
Parameter Value
f841 3 (FD03)
f842 ...
f843 ...
... ...
The value (ex. 1234) of a parameter FD03
is out
p
utted.
Byte Value
0 34
1 12
2 ...
3 ...
... ...
Input Instance152
VF-AS1/PS1
IPE001Z
EtherNet/IP Master

Table of Contents