E6581581
- 16 -
3.2.4.4. FA07 (Frequency reference from comunciation option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
3.2.4.5. FA33 (Torque reference from communication option)
Torque reference is set up by 0.01% unit and the hexadecimal number.
For example, when "torque reference" is set up to 50%, since the minimum unit is 0.01%,
50 / 0.01 = 5000 = 0x1388 (Hex.)
3.2.4.6. FA50 (Terminal output data from communication)
By setting up the data of the bit 0 - 6 of terminal output data (FA50) from communication, setting data (0
or 1) can be outputted to the output terminal.
Please select the functional number 92 - 105 as the selection (f130 - f138, f168, f169) of
the output terminal function before using it.
bit Output TB function name 0 1
0 Communication data 1 (Output TB select No.: 92, 93)
1 Communication data 2 (Output TB select No.: 94, 95
2 Communication data 3 (Output TB select No.: 96, 97
3 Communication data 4 (Output TB select No.: 98, 99
4 Communication data 5 (Output TB select No.: 100, 101
5 Communication data 6 (Output TB select No.: 102, 103
6 Communication data 7 (Output TB select No.: 104, 105
OFF ON
7 to 15 (Reserved) - -
Note: Set 0 to reserved bit.
3.2.4.7. FA51 (Analog output (FM) data from communication)
The data set as the parameter FA51 can output to FM terminal.
The data adjustment range is 0 - 2047 (resolution: 11 bits).
Please select 31 (analog output for communication) as FM terminal meter selection parameter (fmsl)
before using it.
Please refer to "Meter setting and adjustment" Section of the VF-AS1/PS1 instruction manual for details.
3.2.4.8. FA52 (Analog output (AM) data from communication)
The data set as the parameter FA52 can output to AM terminal.
The data adjustment range is 0 - 2047 (resolution: 11 bits).
Please choose 31 (analog output for communication) as AM terminal meter selection parameter
(amsl) before using it.
Please refer to "Meter setting and adjustment" Section of the VF-AS1/PS1 instruction manual for details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS1 Series and is the answer not in the manual?

Toshiba TOSVERT VF-AS1 Series Specifications

General IconGeneral
CategoryInverter
Input Frequency50/60 Hz ±5%
SeriesVF-AS1
Overload Capacity150% for 60 seconds
Input Voltage3-phase 200 to 240 VAC
Protection DegreeIP20
Ambient Temperature-10 to +50 °C (14 to 122°F) (Open type)
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Ground Fault
Braking UnitBuilt-in
CommunicationRS485
Power Range0.4 to 110 kW
Cooling MethodForced Air Cooling
Operating Temperature-10 to +50 °C (14 to 122°F) (Open type)
AltitudeUp to 1000 m
Output Voltage3-phase, voltage corresponding to input voltage