EasyManua.ls Logo

Toshiba TOSVERT VF-AS1 Series - Assigning IP Addresses (F576-F588); Network Error Detection (F849 - F852)

Toshiba TOSVERT VF-AS1 Series
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581581
- 11 -
3.2.2. Assigning IP addresses (f576-f588)
The drive needs following 3 IP addresses.
1. The drive IP address. (f577 - f580)
2. The subnet mask. (f581 - f584)
3. The gateway IP address. (f585 - f588)
These fields are editable when IP mode (f576) = 0.
If the address has been given by a BOOTP or a DHCP server, these fields are read only.
• The new IP addresses are setting to the parameters (f577 - f588) after dynamic
addressing by a BOOTP or DHCP server.
They can be provided by:
*A BOOTP server (correspondence between the MAC address and the IP addresses).
*Or a DHCP server (correspondence between Device Name and IP addresses).
If an IP address other than 0.0.0.0 has been entered, assignment using a server is
disabled.
The address is assigned according to the IP mode parameter.
f576: IP mode Comments
0 The option module uses the address defined in f577-f588.
1 The option module receives its address from a BOOTP server.
2 The option module receives its address from a DHCP server.
*Device name contains (f792-f799) a valid name.
IMPORTANT: The IP mode parameter may be modified according to the configuration
control attribute of the TCP/IP interface object (CIP standard).
See page 33
3.2.3. Network error detection (f849 - f852)
Display of trip information
err8 (Optional unit fault): Communication error
Related parameter
[f849: Communication2 time-out condition selection]
The range 0: Disconnection detection
1: When communication mode enable
2: 1+Driving operation
The condition of detecting the communication time-out is set.
[f850: (Disconnection detection extended time)]
The range: 0.0 to 100.0 sec.
The waiting time from when a network error occurs can be adjusted. If a network
error continues past the time set in f850, it is recognized as a communication
error and the operation of the inverter follows the setting of f851.
When normal communication returns during the set time, a communication error is
not displayed and operation is continued.

Table of Contents